Uniquip Electrical Supplies — PV Array Rotary DC Isolator

PRA number

2014/14157

Published date

Product description

Rotary DC Isolator used in PV Array applications
PRP - LABELLED ISOLATORS
Identifying features
GEN3DC-25, GEN3DC-32, SPMDCISO25, SPMDCISO32

Other identifying numbers

GEN3DC-25, GEN3DC-32, SPMDCISO25, SPMDCISO32

Reasons the product is recalled

The products internal contacts may have a fault, where a high resistance connection may form.

The hazards to consumers

There is a risk that the DC isolator may overheat and catch fire.

What consumers should do

Shut down the system immediately by following the shut down procedure appearing on the label located in main switchboard or mounted near invertor. If you are unsure or cannot identify types of isolators you have, check operating manual or invoice. If you are still unsure contact the company who sold or installed the system for further advice.

You do not need a electrician to shut down the system, however you should seek assistance from a solar company if you are unsure of how to carry out the shutdown procedure safely.

Electrical Contractors/Installers/consumers:

The DC Isolators are required to be replaced. For a replacement program contact Uniquip by phoning 08 9451 4782, emailing admin@uniquip.net.au or website http://www.uniquip.net.au/prp

Wholesalers/Resellers:

Cease supplying GEN3 / SPM DC Isolators and arrange returns by contacting Uniquip by phoning 08 9451 4782, emailing admin@uniquip.net.au or website http://www.uniquip.net.au/prp for further details.

For further information:

Please direct all questions to Uniquip by phoning 08 9451 4782, emailing admin@uniquip.net.au or website http://www.uniquip.net.au/prp

Traders who sold this product

Sold through Electrical Wholesalers or direct to solar contractors / installlers

Where the product was sold

Queensland
Western Australia

Dates available for sale

-

Responsible regulator

Electrical Safety Office (QLD) is the responsible regulator for this recall.